Isolation amplifier (intrinsically safe) Typ: KFA6-SR2-Ex1.W / KFA6-SR2-Ex2.W

Application: Isolating switch amplifier with intrinsically safe control circuit class [Ex ia] IIC for inductive contacts according to DIN 19234

or NAMUR or mechanical contacts in hazardous industrial plants.

Get offer
Case
NORYL SE 0 (self extinguishing)
Case dimensions
B x H x T : 20 x 119 x 115 mm
Mounting
Snap mounting on rail: 35 mm to EN 60715
Weather protection
IP 20 to EN 60529
Wiring
Self-opening instrument terminals cable cross section: up to 2,5 mm²
Power supply
115/230 V AC
Power consumption
< 2,3 w Inputs (intrinsically safe) No load voltage UA0 : approx. 8 VDC Short circuit current IAK : approx. 8 mA Switching point : 1,2 - 2,1 mA Switching hysteresis : approx. 0,2 mA Pulse length/pulse interval : ≥10 ms / ≥10 ms Lead breakage monitoring : I ≤ 0,1 μA
Data according to the certificate of conformity
PTB 00 ATEX 2081 Max. voltage U0 : 10,6 VDC Max. current IK: 19,1 mA Max. power Pmax : 51 mW Ignition protection class : [Ex ia] Explosion group : IIC
Outputs (not intrinsically safe)
2 potential free make contacts Contact loading AC : 253 V / 2 A : cosφ = 0,7 Contact loading DC : 40 V / 2 A
Switching rate
Max. : 5Hz
Permissible temperatures Tmin / Tmax
Ambient temperature: - 20 ... + 60°C
Bestell-Nr.
KFA6-SR2-Ex1.W: 390762 / KFA6-SR2-Ex2.W: 390763
Option
See technical data sheet
  • product data