Isolation amplifiers (intrinsically safe) Typ: KFD2-SR2-Ex1.W / KFD2-SR2-Ex1.W

Application: Isolating switch amplifier with intrinsically safe control circuit class [Ex ia] IIC for inductive contacts according to DIN 19234

or NAMUR or mechanical contacts in hazardous industrial plants.

Get offer
Case
Macrolon
Case dimensions
B x H x T : 20 x 119 x 115 mm
Mounting
Snap mounting on rail : 35 mm to EN 50022
Weather protection
IP 20 to EN 60529
Wiring
Self-opening instrument terminals Cable cross section : up to 2,5 mm²
Power supply
24 V AC
Power consumption
≤ 0,9 w 1 Kanal / ≤ 1,3 w 2 Kanal
Inputs (intrinsically safe)
No load voltage UA0 : approx. 8 VDC Short circuit current IAK : approx. 8 mA Switching point : 1,2 - 2,1 mA Switching hysteresis : approx. 0,2 mA Pulse length/pulse interval : ≥20 ms / ≥20 ms Lead breakage monitoring : I ≤ 0,1 mA
Details of certificate of conformity
PTB 00 ATEX 2081 Max. voltage U0 : 10,6 VDC Max. current IK: 19,1 mA Max. power Pmax : 51 mW Ignition protection class : [Ex ia] Explosion group : IIC
Outputs (non-intrinsically safe)
1 potential free change-over contact Pull in delay : 20 ms Drop out delay : 20 ms Contact loading AC :253 V / 2 A : cosφ = 0,7 Contact loading DC : 40 V / 2 A
Switching rate
Max. : 10Hz
Permissible temperatures Tmin / Tmax
Ambient temperature: - 20 ... + 60°C
Option
See technical data sheet